TRANSFORMER FOR RECTIFIER APPLICATION
325 KVA, 3 PH, 60 Hz, P/N MG-210

Specifications:

      • Dry Type Isolation Transformer, 325 KVA, 3 PH, 60 Hz, P/N MG-210
      • Primary (H1, H2, H3): 460 VAC L-L, 408 Amps, Wye
      • Secondary (X1, X2, X3): 197 VAC L-L, 950 Amps, Delta
      • Taps (2 to 5) are provided on the primary side. See Table A for test results
      • Copper Winding
      • Approvals: UL / CSA listed
      • K Factor: K-1.
      • Temperature Rise: 150 degrees C
      • Open core & coil: 39″W x 19″D x 25″H.
      • Estimated weight: 1530 lbs.­­­

The photo of the transformer is shown below:

 

 

The transformer is tested at 480 VAC, 3 PH, 60 Hz input. The test results are shown in Table A below:

 

 

The schematic diagram is shown below. Primary taps are not shown.

 

 

The primary tap positions are shown blow:

 

 

All our three phase transformers are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.