Specifications:

  • TENV Transformer, 75 KVA, 3 PH, 60 Hz, P/N JE-17
  • Primary (H1, H2, H3): 480 VAC, 90 Amps max, Delta
  • Taps : +2.5%, + 5%, -2.5%, -5%, -7.5%, -10%
  • Secondary (X1, X2, X3): 208 VAC L-L, 208 Amps max, Wye with a neutral X0
  • Enclosure – NEMA 4X-304, 42”H x 33”W x 27”D
  • Insulation – 220°C
  • Temp Rise – 150
  • Windings – Copper
  • Seismic – Yes
  • Weight: 1045 lbs.

The photo of the transformer is shown below:

 

 

The schematic diagram of the transformer is shown below:

 

 

 

 

 

The unit is installed inside a NEMA 4X enclosure as shown below:

 

 

 

 

 

All our NEMA 4X transformers are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.