1 MVA DRY TYPE TRANSFORMER
Specifications:
- Medium Voltage Dry Type Transformer, 1 MVA, 3 PH, 60 Hz, P/N 8375L
- Primary: 460 VAC, 1255 Amps, Delta
- Secondary: 4000 VAC L-L or 2310 VAC L-N, 144 Amps, Wye
- Secondary taps: 2 @ 2.5% FCAN, 2 @ 2.5% FCBN
- High voltage BIL: 30 KV
- Low Voltage BIL: 10 KV
- Aluminum windings
- Insulation class: 220ºC
- Temperature rise: 150ºC
- NEMA 3R Enclosure: 92″H x 90″W x 56″D
- Estimated weight: 6720 lbs.
The Photo of the transformer inside a NEMA 3R enclosure is shown below:
Features / Options:
High Voltage:
- High Voltage KV BIL: 30
- High Voltage Taps: 2 above, 2 below at 2.5%
- High Voltage Windings: Aluminum
- High Voltage: 4000Y/2310
- HV stub up bus
Low Voltage:
- Low Voltage KV BIL: 1
- Low Voltage Windings: Aluminum
- Low Voltage: 460 D
- LV stub up bus
Core & Coil:
- Factory standard impedance
- Step-up application
- Transformer efficiency is EXEMPT from the requirements of DOE 2016
- Transformer is UL & CSA listed
- Vacuum-pressure impregnated (VPI) windings-Polyester resin
Physical & Environmental:
- 64 dB sound level-ANSI IEEE Standard
- Recommended clearances from walls or other obstructions required for access and ventilation: Front = 36″, Top = 18″, Rear = 12″ (36″ for maintenance purposes)
Finish:
- Standard factory paint process with epoxy paint-paint color ANSI 61 light gray color
Testing:
- Routine test per ANSI C57.12.01 are included
Protection:
- Transformer has a 220 degrees C Insulation System
Enclosure:
- Approximate basic enclosure dimensions: 92″H x 90″W x 56″D
- Total Weight: 6720 lbs.
- Case Size ID: US90
- Case Type: Outdoor (NEMA 3R)
- Continuous ground bus – 600 Amp minimum
- Transformer design is in compliance with the default SDS (Spectral reponse acceleration) values at jobsite. For higher SDS values or OSHPD compliance consult factory
- Transformer enclosure is of knock down design
- Transformer provided with an Outdoor NEMA 3R enclosure with louvers – ANSI Category B construction for installation in areas accessible to authorized personnel only
Remarks:
- Approval / Record drawings lead time: 2 weeks after receipt of coordination information
- Transformer factory did not receive formal Customer Specifications with “Request for Quote”. Price is based strictly on providing ratings, features, options and constructions as described on this quotation only
- Warranty per Factory Terms and Conditions: 12 months after energization or 18 months after shipping, whichever occurs first
The schematic diagram of the transformer is shown below:
To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.