1 MVA DRY TYPE TRANSFORMER

Specifications:

  • Medium Voltage Dry Type Transformer, 1 MVA, 3 PH, 60 Hz, P/N 8375L
  • Primary: 460 VAC, 1255 Amps, Delta
  • Secondary: 4000 VAC L-L or 2310 VAC L-N, 144 Amps, Wye
  • Secondary taps: 2 @ 2.5% FCAN, 2 @ 2.5% FCBN
  • High voltage BIL: 30 KV
  • Low Voltage BIL: 10 KV
  • Aluminum windings
  • Insulation class: 220ºC
  • Temperature rise: 150ºC
  • NEMA 3R Enclosure: 92″H x 90″W x 56″D
  • Estimated weight: 6720 lbs.

The Photo of the transformer inside a NEMA 3R enclosure is shown below:

 

 

Features / Options:

High Voltage:

  • High Voltage KV BIL: 30
  • High Voltage Taps: 2 above, 2 below at 2.5%
  • High Voltage Windings: Aluminum
  • High Voltage: 4000Y/2310
  • HV stub up bus

Low Voltage:

  • Low Voltage KV BIL: 1
  • Low Voltage Windings: Aluminum
  • Low Voltage: 460 D
  • LV stub up bus

Core & Coil:

  • Factory standard impedance
  • Step-up application
  • Transformer efficiency is EXEMPT from the requirements of DOE 2016
  • Transformer is UL & CSA listed
  • Vacuum-pressure impregnated (VPI) windings-Polyester resin

Physical & Environmental:

  • 64 dB sound level-ANSI IEEE Standard
  • Recommended clearances from walls or other obstructions required for access and ventilation: Front = 36″, Top = 18″, Rear = 12″ (36″ for maintenance purposes)

Finish:

  • Standard factory paint process with epoxy paint-paint color ANSI 61 light gray color

Testing:

  • Routine test per ANSI C57.12.01 are included

Protection:

  • Transformer has a 220 degrees C Insulation System

Enclosure:

  • Approximate basic enclosure dimensions: 92″H x 90″W x 56″D
  • Total Weight: 6720 lbs.
  • Case Size ID: US90
  • Case Type: Outdoor (NEMA 3R)
  • Continuous ground bus – 600 Amp minimum
  • Transformer design is in compliance with the default SDS (Spectral reponse acceleration) values at jobsite. For higher SDS values or OSHPD compliance consult factory
  • Transformer enclosure is of knock down design
  • Transformer provided with an Outdoor NEMA 3R enclosure with louvers – ANSI Category B construction for installation in areas accessible to authorized personnel only

Remarks:

  • Approval / Record drawings lead time: 2 weeks after receipt of coordination information
  • Transformer factory did not receive formal Customer Specifications with “Request for Quote”. Price is based strictly on providing ratings, features, options and constructions as described on this quotation only
  • Warranty per Factory Terms and Conditions: 12 months after energization or 18 months after shipping, whichever occurs first

The schematic diagram of the transformer is shown below:

 

 

To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.