(714) 624-4740 quote@lcmagnetics.com

DRY TYPE MEDIUM VOLTAGE AUTO TRANSFORMER, 3 MVA, P/N 8407L

We are REPLACEMENT Transformer Specialists

 

We are OBSOLETE Transformer Specialists

 

We are URGENT Transformer Specialists

 

How can we help?

L/C Magnetics Team, celebrating 32 years in business

Specifications:

  • Dry Type Medium Voltage Transformer, 3 MVA, 3 PH, 60 Hz, P/N 8407L
  • Primary: 13800 VAC L-L
  • Secondary: 6900 / 8970 / 11040 VAC L-L
  • High Voltage BIL: 60 KV
  • Aluminum windings
  • Class: AA
  • Temperature rise: 150 degrees C
  • Indoor enclosure: 108″H x 108″W x 60″D approximately
  • Estimated weight: 14500 lbs.

The photo of the transformer is shown below:

 

 

Features / Options:

High Voltage:

  • High Voltage KV BIL: 60
  • High Voltage Taps: 50% – 60% – 80%
  • High Voltage Windings: Aluminum
  • High Voltage: 13800
  • HV stub up bus

Low Voltage:

  • Low Voltage Windings: Aluminum

Core & Coil:

  • Factory standard impedance
  • Motor starting not to exceed 6 times during a 24-hour period
  • Transformer efficiency is EXEMPT from the requirements of DOE 2016
  • Vacuum-pressure impregnated (VPI) windings-Polyester resin

Physical & Environmental:

  • Recommended clearances from walls or other obstructions required for access and ventilation: Front = 36″, Top = 18″, Rear = 12″ (36″ for maintenance purposes)

Finish:

  • Standard factory paint process with epoxy paint-paint color ANSI 61 light gray color

Testing:

  • Routine test per ANSI C57.12.01 are included

Protection:

  • Transformer has a 220 degrees C Insulation System

Enclosure:

  • Approximate basic enclosure dimensions: 108″H x 108″W x 60″D
  • Total Weight: 14500 lbs.
  • Case Size ID: US108
  • Case Type: Indoor
  • Continuous ground bus – 600 Amp minimum
  • Transformer design is in compliance with the default SDS (Spectral reponse acceleration) values at jobsite. For higher SDS values or OSHPD compliance consult factory
  • Transformer enclosure is of knock down design
  • Transformer provided with an Indoor NEMA 1 enclosure with vent slots – ANSI Category C construction for installation in areas accessible to authorized personnel only

Remarks:

  • Approval / Record drawings lead time: 2 weeks after receipt of coordination information
  • Transformer factory did not receive formal Customer Specifications with “Request for Quote”. Price is based strictly on providing ratings, features, options and constructions as described on this quotation only
  • Warranty per Factory Terms and Conditions: 12 months after energization or 18 months after shipping, whichever occurs first

The schematic diagram of the transformer is shown below:

 

 

The details of the transformer are shown below:

 

 

To discuss your specific application, please call our number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.