SINGLE TURN HIGH CURRENT TRANSFORMERS
5 VAC, 2000 AMPS, P/N 19454
Specifications:
- High Current Transformer: 10 KVA, 1 PH, 60 Hz, P/N 19454
- Primary: 220 VAC, 46 Amps
- Secondary: 5 VAC, 2000 Amps
- If 220 VAC input power is connected to Terminals (1 and 2), then secondary output voltage will be 5.23 VAC
- If 220 VAC input power is connected to Terminals (1 and 3), then secondary output voltage will be 5 VAC
- Coupling between primary and secondary is minimal. Higher output voltage drop is expected on the secondary side.
- Primary copper bus bars 1/8” x 5/8” with one hole, copper windings
- Window provided for customer supplied copper rod is 6” x 6”
- Open Core & Coil: 15”W x 12”H x 15”D, 270 lbs. approximately
The photo of the transformer is shown below:
The schematic diagram is shown below:
To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.