SINGLE TURN HIGH CURRENT TRANSFORMER
60 KVA, SECONDARY: 10 VAC, 6000 AMPS, P/N 18699C
Specifications:
- Single Turn High Current Transformer: 60 KVA, 1 PH, 60 Hz, P/N 18699C
- Primary: 600 VAC, 100 Amps
- Secondary: 10 VAC, 6000 Amps, 1 turn, (secondary is customer supplied copper rod)
- Loose primary to secondary coupling may cause the output voltage to drop
- If 600 VAC is connected to (1, 2), output is 10.5 VAC
- If 600 VAC is connected to (1, 3), output is 10.0 VAC
- If 600 VAC is connected to (1, 4), output is 9.5 VAC
- Primary copper bus bars are 1/4” x 1” with one hole
- Window provided for customer copper bus bar is 5” x 5”
- Copper windings.
- Approvals: None
- Open core & coil: 27”W x 20”D x 16”H
- Estimated shipping weight: 1000 lbs.
The photo of the transformer is shown below:
The schematic diagram is shown below:
To discuss your specific application, please call us at (714) 624-4740, or send us an email at quote@lcmagnetics.com.