Specifications:
- High Current Transformer, 6 KVA, 1 PH, 60 Hz, P/N 19643
- Primary: 240 VAC, 25 Amps
- Secondary: 4 VAC, 1500 Amps
- Copper windings.
- Approvals: None
- Two J Thermocouples are installed inside the transformer. One in the primary winding and one in the secondary winding.
- Primary copper bus bars are 1/8″ x 5/8″ with one hole
- Secondary copper bus bars are 3/8” x 4” with one hole
- Open core & coil: 9”W x 18”D x 8.25”H.
- Weight: 150 lbs. approx.
The photo of the transformer is shown below:
The schematic diagram is shown below: