SINGLE PHASE HIGH CURRENT TRANSFORMER
5 KVA, OUTPUT 2 VAC, 2500 AMPS, P/N 19049B

Specifications:

    • High current Transformer, 5 KVA, 1 PH, 60 Hz, P/N 19049B
    • Primary (1 to 9): 220 VAC, 23 Amps
    • Secondary (X1, X2): 1.6 VAC to 2.3 VAC, 2500 Amps max. See page 2 for output voltages
    • Copper windings
    • Approvals: None
    • Primary copper bus bars are 1/8″ x 5/8″ with one hole
    • Secondary copper bus bars are 5″ x 4″ x 3/8″ thick with one hole
    • Open core & coil: 9″W x 9″H x 18″D
    • Estimated weight: 150 lbs.

The photo of the transformer is shown below:

 

 

 

The output voltages are shown below:

    • If 220 VAC is connected to (1, 9), then output (X1, X2) is 1.60 VAC
    • If 220 VAC is connected to (1, 8), then output (X1, X2) is 1.71 VAC
    • If 220 VAC is connected to (1, 7), then output (X1, X2) is 1.80 VAC
    • If 220 VAC is connected to (1, 6), then output (X1, X2) is 1.90 VAC
    • If 220 VAC is connected to (1, 5), then output (X1, X2) is 2.00 VAC
    • If 220 VAC is connected to (1, 4), then output (X1, X2) is 2.09 VAC
    • If 220 VAC is connected to (1, 3), then output (X1, X2) is 2.20 VAC
    • If 220 VAC is connected to (1, 2), then output (X1, X2) is 2.30 VAC

The schematic diagram of the transformer is shown below:

 

 

 

To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.