SCOTT T TRANSFORMER
52 KVA, P/N 19530N

Scott T Transformers offer two single-phase outputs and not one single-phase output.

Scott T Transformers cannot be used to create only one single-phase output.

Specifications:

  • Scott T Transformer, 52 KVA, 3 PH, 60 Hz, P/N 19530N
  • Primary (1, 2, 3): 480 VAC L-L, 62.5 Amps
  • Secondary MAIN (4, 5): 52 VAC, 500 Amps
  • Secondary TEASER (6, 7): 52 VAC, 500 Amps
  • Copper windings
  • Primary copper bus bars are 1/4” x 1” with one hole
  • Secondary copper bus bars are 1/4” x 2” with one hole
  • Indoor enclosure: 36”H x 28”W x 18”D
  • Estimated shipping weight: 600 lbs.

The photo of the transformer and the enclosure is shown below:

 

 

The schematic diagram is shown below:

 

 

To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.