SCOTT T TRANSFORMER
30 KVA, P/N 19465N1

Scott T Transformers offer two single-phase outputs and not one single-phase output.

Scott T Transformers cannot be used to create only one single-phase output.

Specifications:

  • Scott T Transformer, 30 KVA, 60 Hz, P/N 19465N1
  • Primary Input (H1, H2, H3): 480 VAC, 36 Amps
  • MAIN Output (1 to 5): 0 / 90 / 96 / 100 / 106 VAC, 167 Amps, 15 KVA
  • TEASER Output (1 to 5): 0 / 90 / 96 / 100 / 106 VAC, 167 Amps, 15 KVA
  • Copper windings
  • Input copper bus bars are 1/8″ x 5/8″, output copper bus bars 1/4” x 1”
  • MAIN and TEASER are 90 degrees out of phase. Jumper will be provided
  • Indoor enclosure, 36″H x 28″W x 18″D, Estimated weight: 700 lbs

The photo of the Scott T Transformer is shown below:

 

 

The schematic diagram is shown below:­­­­

 

 

 

To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.