SCOTT T TRANSFORMER
150 KVA, P/N 19715N

Scott T Transformers offer two single-phase outputs and not one single-phase output.

Scott T Transformers cannot be used to create only one single-phase output.

Specifications:

    • Scott T Transformer, 150 KVA, 60 Hz, P/N 19715N
    • Primary Input (H1, H2, H3): 480 VAC, no taps, 180 Amps, 150 KVA
    • MAIN Output (X1, X2, X3): 120 / 240 VAC ± 13%, 313 Amps max
    • TEASER Output (Y1, Y4, Y5): 120 / 240 VAC ± 13%, 313 Amps max
    • Copper windings.
    • Approvals: None
    • Primary Copper bus bars are 1/4″ x 1″ with two holes
    • Main/Teaser Copper bus bars are 1/4″ x 1 1/2″ with two holes
    • MAIN and TEASER are 90° out of phase
    • Indoor floor mount enclosur­­e: 50″H x 36″W x 26″D.
    • Estimated weight: 2500 lbs.

The schematic diagram is shown below:

Schematic Diagram

 

The Photo of the Primary (H1, H2, and H3) is shown below:

 

 Primary Side

 

The photo of the Secondary side is shown below:

The MAIN is (X1, X2)  = 120 VAC and (X1, X3) = 240 VAC. It is available on the MAIN transformer winding

The TEASER is (Y1, Y4)  = 120 VAC and (Y1, Y5) = 240 VAC. It is available on the two Buck-Boost transformers winding.

The TEASER output was lower so we had to use Buck-Boost transformers to raise the output per requirement.

Secondary Side

The photo of the enclosure (50”H x 36”W x 26”D) is shown below:

 

 

To discuss your specific application, please call our number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.