SCOTT T TRANSFORMER
50 KVA, P/N 18768N

Scott T Transformers offer two single-phase outputs and not one single-phase output.

Scott T Transformers cannot be used to create only one single-phase output.

Specifications:

  • Scott T Transformer, 50 KVA, P/N 18768N
  • Input: 480 VAC, 3 PH, 60 HZ, 65 Amps
  • Output MAIN: 240 VAC, 104 Amps, 1 PH
  • Output TEASER: 240 VAC, 104 Amps, 1 PH
  • Indoor enclosure: 42” H x 32” W x 22” D
  • MAIN and TEASER are 90° out of phase.
  • T1/T2 Jumper is provided with the unit.

The photo of the 50 KVA Scott T Transformer is shown below:

 

18768N_ST

 

MAIN and TEASER outputs must not be connected in series or in parallel. This causes current imbalance on the primary side. The schematic diagram is shown below:

 

18768N_ST

 