SCOTT T TRANSFORMER
30 KVA, P/N 18726N
Scott T Transformers offer two single-phase outputs and not one single-phase output.
Scott T Transformers cannot be used to create only one single-phase output.
Specifications:
- Scott T Transformer, 30 KVA, P/N 18726N
- Input: 480 VAC, 36 Amps, 3 PH, 60 HZ
- Output MAIN: 208 VAC, 72.11 A, 1 PH
- Output TEASER: 208 VAC, 72.11 A, 1 PH
- Indoor enclosure: 36” H x 28” W x 18” D
- MAIN and TEASER are 90° out of phase.
- T1/T2 Jumper is provided with the unit.
The photo of the Scott transformer is shown below:
MAIN and TEASER outputs must not be connected in series or in parallel. This causes current imbalance on the primary side. The schematic diagram is shown below:
To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.