NEMA 1 SCOTT T TRANSFORMER, 100 KVA

ALUMINUM WINDING, P/N MG-53

Specifications:

    • Scott T Transformer, 100 KVA, 3 PH, 60 Hz, P/N MG-53
    • Primary (H1, H2, and H3): 480 VAC L-L, 120 Amps, no taps
    • Secondary MAIN (X3, X4): 194 VAC, 258 Amps
    • Secondary TEASER (X1, X2): 194 VAC, 258 Amps
    • Aluminum windings
    • Approvals: CSA / UL listed
    • Temperature rise: 150 degrees C, K-factor: K-1, Sound level: 50
    • NEMA 1 enclosure: 40.5″H x 31.5″W x 21.75″D, estimated weight: 900 lbs

Photo of the Primary (H1, H2, and H3) is shown below:

 

 

Photo of the Secondary MAIN (X3, X4) and Secondary TEASER (X1, X2) is shown below:

 

 

 

 

 

The schematic diagram is shown below:

 

 

 

Details of the enclosure are shown below:

 

 

To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.