HIGH CURRENT SECONDARY TAP TRANSFORMER
34 KVA, P/N 18774

Specifications:

    • Transformer: 34 KVA, 3 PH, 60 Hz to 120 Hz, P/N 18774
    • Primary: 480 VAC, 40 Amps, Delta
    • Secondary Tap 1: 24 VAC, 800 Amps, Wye
    • Secondary Tap 2: 48 VAC, 400 Amps, Wye
    • Secondary Tap 3: 96 VAC, 200 Amps, Wye
    • Secondary Tap 4: 144 VAC, 135 Amps, Wye
    • Primary bus bar: ¼” x 1”
    • Secondary tap 1 bus bar: 3/8” x 2 ½”
    • Secondary tap 2, 3, 4 bus bar: ¼” x 1
    • Open core and coil: 18”H x 22”W x 20”D
    • Copper winding construction
    • Weight: 400 lbs approximately

The photo of the transformer is shown below:

 

18774_MT

 

The schematic diagram is shown below:

 

18774_MT

 

To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.