Specifications:

      • Scott T Transformer, 15 KVA, 60 Hz, P/N 9306L1
      • Primary Input (1, 2, 3): 208 VAC, 41.6 Amps, 15 KVA
      • MAIN Output (4, 5): 120 VAC, 62.5 Amps, 7.5 KVA
      • TEASER Output (6, 7): 120 VAC, 62.5 Amps, 7.5 KVA
      • Aluminum Windings
      • Approvals: UL / CSA listed
      • K Factor: K-1
      • Temperature Rise: 150 degrees C
      • Indoor/Outdoor Enclosure: 21.00″W x 28.00″H x 14.00″D
      • Estimated weight: 245 lbs.

The schematic diagram is shown below:

 

 

The details of the enclosure are shown below:

 

The photo of the enclosure is shown below:

 

All our transformers are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.