SCOTT T TRANSFORMER
100 KVA, P/N MG-53
Scott T Transformers offer two single-phase outputs and not one single-phase output.
Scott T Transformers cannot be used to create only one single-phase output.
Specifications:
-
- Scott T Transformer, 100 KVA, 3 PH, 60 Hz, P/N MG-53
- Primary (H1, H2, and H3): 480 VAC L-L, 120 Amps, no taps
- Secondary MAIN (X3, X4): 194 VAC, 258 Amps
- Secondary TEASER (X1, X2): 194 VAC, 258 Amps
- Aluminum windings
- Approvals: CSA / UL listed
- Temperature rise: 150 degrees C, K-factor: K-1, Sound level: 50
- NEMA 1 enclosure: 40.5″H x 31.5″W x 21.75″D, estimated weight: 900 lbs
Photo of the Primary (H1, H2, and H3) is shown below:
Photo of the Secondary MAIN (X3, X4) and Secondary TEASER (X1, X2) is shown below:
Photo of the Scott T Transformer is shown below:
The schematic diagram is shown below:
Details of the enclosure are shown below:
All our transformers are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.