Specifications:

    • Dry Type Substation Transformer, 4.375 MVA, 3 PH, 60 Hz, P/N MG-260
    • Primary: 13800 VAC L-L, Wye
    • Primary Taps: 2-2.5% FCAN and 2-2.5% FCBN
    • Secondary: 12460 VAC L-L, Delta
    • Aluminum Windings
    • Approvals: UL / CSA listed
    • K factor: K1 rated
    • Temperature Rise: 150 degrees C
    • NEMA 3R Enclosure: 132″W x 122″H x 78″D
    • Estimated Weight: 18170 lbs.

The schematic diagram is shown below:

 

 

The details of the enclosure are shown below:

 

 

The photo of the enclosure is shown below:

 

 

All our transformers are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.