Specifications:

  • Dry Type Transformer, 550 KVA, 3 PH, 50 Hz, P/N MG-280
  • Primary: 380 VAC L-L, Delta
  • Primary Taps: 2-2.5% FCAN and 2-2.5% FCBN
  • Secondary: 460 VAC L-L Wye with a neutral, 266 VAC L-N
  • Aluminum Windings
  • Approvals: UL / CSA listed
  • CE labeled
  • K Factor: K-1
  • Temperature Rise: 150 degrees C
  • Outdoor Enclosure with Rain Hood: 66.00″H x 50.50″W x 40.50″D
  • Estimated weight: 3800 lbs.

The schematic diagram is shown below:

The details of the enclosure are shown below:

The photo of the enclosure  is shown for reference:

 

All our transformers are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.