TRANSFORMER FOR DC TO DC APPLICATION

200 KVA, 30 KHz, P/N 9582L

 The customer application is shown below:

 

 

Specifications:

    • Isolation Transformer, 200 KVA, 1 PH, 30 KHz, P/N 9582L
    • Primary (1, 2): 800 V, 250 Amps
    • Secondary (3, 4): 475 V, 210 Amps
    • Secondary (5, 6): 475 V, 210 Amps
    • Primary winding will be sandwiched between the two secondary windings
    • Copper foil winding
    • Approvals: None
    • Ferrite Core construction
    • Primary and secondary copper bus bars are 1/4″ x 1″ with one hole or TBD
    • Open core and coil: 9.5″H x 8.0″W x 10.0″D or TBD
    • Power loss: not to exceed 750 W
    • Encapsulated: None
    • Mounting provision: None
    • Water Cooled: None
    • Estimated weight: 50 lbs. or TBD
    • Customer Application: DC to DC Inverter

A photo of a similar transformer is shown below:

 

 

The schematic diagram is shown below:

 

 

We can build similar transformers with a frequency range from 30 KHz to higher and a power rating of 500 KVA max. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.