CE APPROVED TRANSFORMER 15 KVA, PRIMARY 400 VAC DELTA, SECONDARY 208 VAC DELTA, ALUMINUM, P/N MG-133
Specifications:
- CE Approved Transformer, 15 KVA, 3 PH, 50/60 Hz, P/N MG-133
- Primary: 400 VAC L-L, Delta, 22 Amps
- Primary taps: 2-2.5% FCAN and 4-2.5% FCBN, not shown in the schematic diagram
- Secondary: 208 VAC L-L, Delta, 42 Amps
- Aluminum windings
- CE Approved
- UL/CSA Approved
- K-factor: K-1
- Temperature rise: 150 Degrees C
- NEMA 3R enclosure: 28”H x 21”W x 14”D
- Estimated weight: 270 lbs.
The photo of the transformer and the enclosure is shown below:
The schematic diagram is shown below:
The Primary Taps are shown below in Table A. Three jumpers are used to select primary of 400 VAC, 3 PH L-L, Delta.
All our three phase transformers are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.