POLE MOUNTED NEUTRAL GROUNDING REACTOR, P/N 9886L
Specifications:
- Dry Type Pole Mounted Neutral Grounding Reactor, P/N 9886L
- Each inductor is rated for 4 mH, 184 Amps, 60 Hz. (two inductors in one enclosure)
- Enclosure is Totally Enclosed Non-Ventilated Stainless Steel, non-painted.
- Enclosure can be installed on a pole.
- Secondary Output from pole mounted transformers is 480 VAC L-L, 277 VAC L-N.
- The two inductors are provided to be connected from the secondary neutral to ground.
- The output terminals for one inductor is (1, 2) and is available outside the enclosure.
- The output terminals for one inductor is (3, 4) and is available outside the enclosure.
- Enclosure Dimensions are 45″ W x 25″ H x 25″ D.
- Total Weight: 800 lbs. or TBD
- Copper Windings
- Approval: None
The schematic of the two inductors in one enclosure is shown below:

The dimensions of each inductor is shown below:

The dimensions of the two inductors in one enclosure is shown below:

To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.