Specifications:
- Transformer: 40 KVA, 1 PH, 60 Hz, P/N 2AAAE-18699B
- Primary: 600 VAC, 67 Amps, 60 Turns
- Secondary: 10 VAC, 4000 Amps, 1 turn of customer supplied cable.
- Primary to secondary ratio: 60 to 1
- Window provided for customer cable: 5” x 5”
- Primary copper bus bar: 1/4” x 1” with one hole
- Open Core & Coil: 17”H x 21”W x 20”D approximately
- Estimated weight: 700 lbs. approx.
A photo of the transformer is shown below:
The schematic of the transformer is shown below:
All our low voltage transformers are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.