Isolation Delta to Wye with Metal Ground, 15 KVA, 5U
Specifications:
- Isolation Delta to Wye Transformer with Metal Ground, 15 KVA, 3 PH, 60 Hz, P/N 5U-MG-198
- Primary (H1, H2, H3): 480 VAC L-L, Delta.
- Primary Taps: 2-2.5% FCAN and 4-2.5% FCBN
- Secondary (X1, X2, X3): 400 VAC L-L, Wye with a neutral (X0), 231 VAC L-N
- Metal Ground (GND) connection available inside the enclosure
- Customer may connect (X0) to Metal Ground (GND) if necessary, with a jumper (jumper not provided)
- Aluminum Windings.
- Approvals: UL / CSA listed
- K Factor: K-1.
- Temperature Rise: 150 degrees C
- Indoor/Outdoor enclosure: 21.00″W x 14.00″D x 28.00″H.
- Estimated weight: 245 lbs.
The photo of the transformer inside the enclosure is shown below:
The schematic diagram is shown below:
The Primary Taps are shown below in Table A. Three jumpers are used to select primary of 480 VAC L-L, 3 PH, Delta.
The photo of the unit before shipment is shown below:
To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.