The customer application is shown below. The CLR (current limiting reactor) consists of three gapped inductors inside three separate enclosures. The input power is 13800 VAC, 3 PH, 60 Hz. Circuit breakers are supplied by the customer. A 151 volts drop is observed at 600 amps continuous current.
The Calculations of inductance value for 600 amps continuous and 55000 amps fault current are shown below:
Assuming 55000 Amps Fault Current, The inductance Value is
- V = 2 x pi x F x L x I (Fault Current)
- L = 13800 / (2 x pi x F x I (Fault Current))
- L= 13800 / (2 x 3.142 x 60 x 55000) = 665.4 uH
Voltage Drop Across The CLR At 600 Amps Continuous Is
- V = 2 x pi x F x L x I (Continuous Current)
- V = 2 x 3.142 x 60 x (665.4 x 10-6) x 600
- V = 151 Volts
The voltage drop across the CLR at different current levels is shown in Table A:
Table A
Voltage Drop Across The CLR | Current Thru The CLR |
151 Volts | 600 Amps |
252 Volts | 1000 Amps |
2520 Volts | 10000 Amps |
5040 Volts | 20000 Amps |
7560 Volts | 30000 Amps |
10800 Volts | 40000 Amps |
12600 Volts | 50000 Amps |
13800 Volts | 55000 Amps |
The details of each gapped inductor (front and side view) with enclosure are shown below:
Specifications:
- Gapped Inductor with enclosure, P/N 6440L
- L (1, 2) = 665.4 uH ± 25 %, 600 Amps
- Copper bus bars are 2 1/2″ x 13″ x 3/8” thick
- Six of 500 KCMIL compression lugs can be connected to each bus bar.
- Copper winding construction
- NEMA 3R Enclosure, 50″H x 36″W x 34″D
- Estimated weight of each gapped inductor inside the enclosure: 500 lbs
The CLR consists of three inductors. Each inductor is housed inside a separate indoor enclosure as shown below. Input/output cables can be from the top or the bottom of the enclosure.