Air Core Reactor 40 uH, 600 Amps Continuous
P/N 6908L
Specifications:
- Air Core Reactor, P/N 6908L
- Inductance = 40 uH
- Impedance = 0.015 Ohms
- Continuous current: 600 Amps
- Available fault current: (TBD) Amps
- Limit fault current: 18500 Amps
- Voltage: 480 VAC L-L, 277 VAC L-N
- Voltage drop: 3.2%
- Terminal: NEMA 4 bolt hole pattern
- Three reactors are stacked one above the other in a vertical fashion
- Enclosure with louvers: 70”H x 30”W x 30”D approximately
- ANSI TR-202 base insulators (1 for each reactor)
The customer application is shown below:
The photo of the three inductors inside the enclosure is shown below. Three reactors are stacked one above the other in a vertical fashion.
All our CLR’s are custom built to order. To discuss your specific application, please call our number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.