Specifications:

  • Air Core Reactor, P/N 6885L
  • Inductance = 10 uH
  • Impedance = 0.0038 Ohms
  • Continuous current: 1600 Amps
  • Available fault current: 70000 Amps
  • Limit fault current: 42000 Amps
  • Voltage: 480 VAC L-L, 277 VAC L-N
  • Voltage drop: 2.2%
  • Terminal: NEMA 4 bolt hole pattern
  • Three reactors are stacked one above the other in a vertical fashion
  • Enclosure with louvers: 97”H x 60”W x 60”D
  • ANSI TR-202 base insulators (1 for each reactor)

The customer application is shown below.
AIR CORE REACTOR, 10 uH, 1600 AMPS CONTINUOUS, P/N 6885L Schematic Diagram
The details of each Air Core Reactor are shown below.
AIR CORE REACTOR, 10 uH, 1600 AMPS CONTINUOUS, P/N 6885L Schematic Diagram
Notes:

  • Minimum spacing center to center is 29”
  • Outside coil diameter is 17”
  • Terminals: NEMA 4 bolt hole pattern
  • Approximate weight: 330 lbs
  • 3 seconds thermal: 53.3 KA, mechanical peak: 141.4 KA
  • Minimum clearance to small magnetic objects not forming closed loops
    1. A = 20.5”
    2. B = 3”
  • For large magnetic objects & magnetic objects forming closed loops
  1. A = 29”
  2. B = 12”
  • Must be weather protected

All our auto transformers are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at info@LCMAGNETICS.COM.