Air Core Reactor 0.004 mH, 4000 Amps Continuous
P/N 6906L
Specifications:
- Air Core Reactor, P/N 6906L
- Inductance = 0.004 mH
- Impedance = 0.002 Ohms
- Continuous current: 4000 Amps
- Available fault current: (TBD)
- Limit fault current: 140000 Amps
- Voltage: 480 VAC L-L, 277 VAC L-N
- Voltage drop: 3%
- Terminal: NEMA 24 bolt hole pattern
- Three reactors are required for one complete CLR system
- Each reactor is housed inside a separate enclosure, 90”H x 90”W x 90”D
- ANSI TR-202 base insulators (1 for each reactor)
- Aluminum pedestal (1 for each reactor)
The customer application is shown below.
The photo of the enclosure and the Single Air Core Reactor is shown below. Each Single Air Core Reactor is housed inside a separate enclosure. Three enclosures are required for one complete CLR system.
All our CLR’s are custom built to order. To discuss your specific application, please call our number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.