(714) 624-4740 quote@lcmagnetics.com

Specification:

  • Air Core Inductor, P/N 8174L
  • L (1, 2) = 61 uH ± 25 %, 600 Amps continuous
  • Fault current limit: 6000 Amps
  • Voltage available to the load will be reduced from 480 VAC L-L to 456 VAC L-L due to the CLR
  • Copper bus bars are 2″ x 1/4” thick
  • Copper winding construction
  • Three Air Core Inductors are required for one complete CLR system
  • Three Air Core Inductors is installed vertically in one stainless steel enclosure (72″H x 48″W x 48″D)
  • Estimated weight for three inductors in one enclosure: (TBD) lbs.

The customer application is shown below:

 

Air Core Inductor, 61 Uh, 600 Amps, P/N 8174L Schematic Diagram

 

The photo of the the inductor and the stainless steel enclosure is shown below. Three reactors are stacked one above the other in a vertical fashion.

 

Air Core Inductor, 61 Uh, 600 Amps, P/N 8174L

 

Three reactors are stacked one above the other in a vertical fashion as shown below:

 

Air Core Inductor, 61 Uh, 600 Amps, P/N 8174L Schematic Diagram

 

All our inductors are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at info@LCMAGNETICS.COM.