Specifications:
- CLR, P/N TR-15B
- Inductance = 3.8 mH +/- 4%
- Ohm = 1.4326 Ohms
- Continuous current: 200 Amps
- Current limit: 1.67 kA
- Rated voltage: 4.16 KV
- Frequency: 60 Hz
- BIL across coil: 75 kV
- BIL across base insulator: 110 kV
- Available fault current: 4.275 kA
- Number of coil per phase: 1
- Mounting (side-by-side or three phase stack): Three Phase Stack
- MC1 / MC2 above and below edge of coil: 3 / 15 inch
- MC1 / MC2 from side to the edge of coil: 7/ 10 inch
- Steel enclosure: 72″W x 72″D x 146″H
- estimated weight: 700 lbs.
The customer application is shown below:
The details of the CLR are shown below. Three CLR’s are used for a three phase applications. Three CLR’s are installed three stack high. Drawing belongs to Trench Limited.
All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.