CLR, 2.63 mH, 300 Amps, 600 VAC
P/N TR-02
Specifications:
-
- CLR, P/N TR-02
- Inductance = 2.63 mH +/- 4%
- Ohm = 0.99 Ohms
- Continuous current: 300 Amps
- Current limit: 1 kA
- Rated voltage: 600 VAC
- Frequency: 60 Hz
- BIL across coil: 45 kV
- BIL across base insulator: 95 kV
- Mechanical peak current: 2.55 kA
- Losses at fundamental current (75 C ) per phase: 2.9 kW
- Number of coil per phase: 1
- Mounting (side-by-side or three phase stack): side-by-side
- MC1 / MC2 above and below edge of coil: 9 / 26 inches
- MC1 / MC2 from side to the edge of coil: 13 / 17 inches
- Overall dimensions: 42″x 42″ x 44″H
- estimated weight: 840 lbs.
The customer application is shown below:
The details of the CLR are shown below. Three CLR’s are used for a three phase applications. Three CLR’s are installed side-by-side. Drawing belongs to Trench Limited.
All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.