CLR, 1.67732 mH, 105 Amps, 13.8 kV
P/N TR-05

Specifications:

  • CLR, P/N TR-05
  • Inductance = 1.67732 mH +/- 4%
  • ohm = 0.632 Ohms
  • Continuous current: 105 Amps
  • Current limit: 1.4 kA
  • Rated voltage: 13.8 kV
  • Frequency: 60 Hz
  • BIL across coil: 110 kV
  • BIL across interphase insulator: 150 kV
  • BIL across base insulator: 110 kV
  • Mechanical peak current: 3.57 kA
  • Number of coil per phase: 1
  • Mounting (side-by-side or three phase stack): side-by-side
  • MC1 / MC2 above and below edge of coil: 3 / 11 inches
  • MC1 / MC2 from side to the edge of coil: 5 / 8 inches
  • Overall dimensions: 42″W x 42″L x 44″H
  • estimated weight: 250 lbs.

The customer application is shown below:

 

 

The details of the CLR are shown below. Three CLR’s are used for a three phase applications. Three CLR’s are installed side-by-side. Drawing belongs to Trench Limited.

 

 

 

All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.