CLR, 1.06 mH, 400 Amps, 13.8 kV
P/N TR-09

Specifications:

  • CLR, P/N TR-09
  • Inductance = 1.06 mH +/- 4%
  • Ohm = 0.4 Ohms
  • Continuous current: 400 Amps
  • Current limit: 5 kA
  • Rated voltage: 13.8 kV
  • Frequency: 60 Hz
  • BIL across coil: 95 kV
  • BIL across base insulator: 95 kV
  • Mechanical peak current: 25.5 kA
  • Number of coil per phase: 1
  • Mounting (side-by-side or three phase stack): Three Phase Stack
  • MC1 / MC2 above and below edge of coil: 2 / 25 inches
  • MC1 / MC2 from side to the edge of coil: 12 / 16 inches
  • Overall dimensions: 51″W x 51″L x 50″H
  • estimated weight: 375 lbs.

The customer application is shown below:

 

 

The details of the CLR are shown below. Three CLR’s are used for a three phase applications. Three CLR’s are installed tin a three phase high fashion. Drawing belongs to Trench Limited.

 

 

All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.