Specifications:

  • CLR, P/N TR-16
  • Inductance = 0.53 mH +/- 4%
  • Ohm  = 0.2 Ohms
  • Continuous current: 800 Amps
  • Current limit: 20 kA
  • Rated voltage: 13.8 KV
  • Frequency: 60 Hz
  • BIL across coil: 110 kV
  • BIL across base insulator: 110 kV
  • Available fault current: 51 kA
  • Number of coil per phase: 1
  • Mounting (side-by-side or three phase stack): Three Phase Stack
  • Dimensions: 1900 mm H x 1900 mm W x 1400 mm D
  • MC1 / MC2 above and below edge of coil: 175 / 525 mm
  • MC1 / MC2 from side to the edge of coil: 300/ 390 mm
  • Enclosure: None
  • estimated weight: 650 lbs.

The customer application is shown below:

 

 

The details of the CLR are shown below. Three CLR’s are used for a three phase applications. Three CLR’s are installed three stack high. Enclosure is not provided. Drawing belongs to Trench Limited.

 

 

All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.