(714) 624-4740 quote@lcmagnetics.com

Specifications:

  • CLR, P/N TR-13
  • Inductance = 0.452 mH +/- 4%
  • Ohm  = 0.0171 Ohms
  • Continuous current: 800 Amps
  • Current limit: 10 kA
  • Rated voltage: 480 VAC
  • Frequency: 60 Hz
  • BIL across coil: 60 kV
  • BIL across base insulator: 45 kV
  • Available fault current: 25.5 kA
  • Number of coil per phase: 1
  • Mounting (side-by-side or three phase stack): Three Phase Stack
  • MC1 / MC2 above and below edge of coil: 3 / 15 inch
  • MC1 / MC2 from side to the edge of coil: 7/ 10 inch
  • Approx. Packing Dimensions (inch): 90 x 90 x 117
  • estimated weight: 1000 lbs.

The customer application is shown below:

 

 

The details of the CLR are shown below. Three CLR’s are used for a three phase applications. Three CLR’s are installed side-by-side. Drawing belongs to Trench Limited.

 

 

All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.