CLR, 0.275 mH, 3650 Amps, 700 VAC, 1 PH, 60 Hz
P/N TR-22

Specifications:

  • Dry Type CLR, 1 PH, 60 HZ, P/N TR-22
  • Inductance: 0.275 mH
  • Resistance: 0.104 Ohms
  • 3650 Amps continuous
  • Current limit: 3.9 KA
  • Available fault current: 9.94 KA
  • Rated Voltage: 700 VAC, 1 PH, 60 Hz
  • BIL across coil: 45 kV
  • BIL across base insulator: 95 kV
  • Number of coil per phase: 1
  • Mounting (side-by-side or three phase stack): Three Phase Stack
  • MC1 / MC2 above and below edge of coil: 28/66 inch
  • MC1 / MC2 from side to the edge of coil: 28/36 inch
  • Dimensions of each CLR: 50”H x 80”W x 80”D
  • No enclosure
  • Weight: 1900 lbs.

The customer application is shown below:

 

 

The details of the CLR are shown below. No enclosure provided. Drawing belongs to Trench Limited.

 

 

All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.