CLR, 0.134 mH, 1200 Amps, 13800 VAC, 3 PH, 60 Hz
P/N TR-24

Specifications:

    • Dry Type CLR, 3 PH, 60 Hz, P/N TR-24
    • Inductance: 0.134 mH
    • Resistance: 0.0506 Ohms
    • 1200 Amps continuous
    • Current limit: 45000 Amps, symmetrical, 1/2 cycle
    • Available fault current: 63000 Amps, symmetrical, 1/2 cycle
    • Fault duration: 1 second
    • Rated Voltage: 13800 VAC L-L
    • BIL rating: 110 KV
    • Dimensions: 122”H x 54”W x 54”D approximately
    • Three stack high
    • Weight: 1400 lbs approximately
    • Enclosure: None

The customer application is shown below:

 

 

The details of the CLR are shown below. No enclosure provided. Drawing belongs to Trench Limited.

 

 

All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.