CLR, 0.12252 mH, 100 Amps, 600 VAC
P/N TR-08

Specifications:

    • CLR, P/N TR-08
    • Inductance = 0.12252 mH +/- 4%
    • Ohm = 0.046 Ohms
    • Continuous current: 100 Amps
    • Current limit: 5 kA
    • Rated voltage: 600 VAC
    • Frequency: 60 Hz
    • BIL across coil: 45 kV
    • BIL across base insulator: 95 kV
    • Available fault current: 12.75 kA
    • Number of coil per phase: 1
    • Mounting (side-by-side or three phase stack): side-by-side
    • MC1 / MC2 above and below edge of coil: 3 / 1 inches
    • MC1 / MC2 from side to the edge of coil: 2 / 3 inches
    • Overall dimensions: 34″W x 34″L x 26″H
    • estimated weight: 150 lbs.

The customer application is shown below:

 

 

The details of the CLR are shown below. Three CLR’s are used for a three phase applications. Three CLR’s are installed side-by-side. Drawing belongs to Trench Limited.

 

 

All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.