CLR, 0.12252 mH, 100 Amps, 600 VAC
P/N TR-08
Specifications:
-
- CLR, P/N TR-08
- Inductance = 0.12252 mH +/- 4%
- Ohm = 0.046 Ohms
- Continuous current: 100 Amps
- Current limit: 5 kA
- Rated voltage: 600 VAC
- Frequency: 60 Hz
- BIL across coil: 45 kV
- BIL across base insulator: 95 kV
- Available fault current: 12.75 kA
- Number of coil per phase: 1
- Mounting (side-by-side or three phase stack): side-by-side
- MC1 / MC2 above and below edge of coil: 3 / 1 inches
- MC1 / MC2 from side to the edge of coil: 2 / 3 inches
- Overall dimensions: 34″W x 34″L x 26″H
- estimated weight: 150 lbs.
The customer application is shown below:
The details of the CLR are shown below. Three CLR’s are used for a three phase applications. Three CLR’s are installed side-by-side. Drawing belongs to Trench Limited.
All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.