Specifications:

  • CLR, P/N TR-17
  • Inductance = 0.11808 mH +/- 4%
  • Ohm  = 0.0454 Ohms
  • Continuous current: 800 Amps
  • Current limit: 5 kA
  • Available fault current: 25.4 KA
  • Rated voltage: 480 VAC
  • Frequency: 60 Hz
  • BIL across coil: 45 kV
  • BIL across base insulator: 110 kV
  • Number of coil per phase: 1
  • Mounting (side-by-side or three phase stack): Three Phase Stack
  • Enclosure dimensions: 51″ x 51″ x 90″
  • MC1 / MC2 above and below edge of coil: 5/20 inch
  • MC1 / MC2 from side to the edge of coil: 9/12 inch
  • estimated weight: 1000 lbs.

The customer application is shown below:

 

 

The details of the CLR are shown below. Three CLR’s are used for a three phase applications inside an enclosure. Drawing belongs to Trench Limited.

 

 

All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.