Specifications:

    • Dry Type CLR, 3 PH, 60 HZ, P/N TR-25
    • Inductance: 0.05466 mH
    • Resistance: 0.021 Ohms
    • 800 Amps continuous
    • Current limit: 10 KA
    • Available fault current: 39 KA
    • Rated Voltage: 480 VAC, 3 PH, 60 Hz
    • BIL across coil: 45 KV
    • BIL across interphase insulator: 110 KV
    • BIL across base insulator: 110 KV
    • Enclosure: None
    • Dimensions: 48″W x 48″D x 96″H
    • Weight: 540 lbs.

The customer application is shown below:

 

 

The details of the CLR are shown below. No enclosure provided. Drawing belongs to Trench Limited.

 

 

All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at info@lcmagnetics.com.