CLR, 0.04807 mH, 660 Amps, 480 VAC
P/N TR-18X

Specifications:

    • CLR, P/N TR-18X
    • Inductance = 0.04807 mH +/- 4%
    • Ohm  = 0.018 Ohms
    • Continuous current: 660 Amps
    • Current limit: 10000 Amps
    • Available fault current: 28900 Amps
    • Rated voltage: 480 VAC
    • Frequency: 60 Hz
    • BIL across coil: 45 kV
    • BIL across interphase insulator: 95 kV
    • BIL across base insulator: 95 kV
    • Number of coil per phase: 1
    • Mounting (side-by-side or three phase stack): Three Phase Stack
    • MC1 / MC2 above and below edge of coil: 4/12 inch
    • MC1 / MC2 from side to the edge of coil: 8/9 inch
    • Enclosure dimensions: (TBD)
    • estimated weight: 1000 lbs.

The customer application is shown below:

 

 

The details of the CLR are shown below. Three CLR are installed inside one enclosure. Drawing belongs to Trench Limited.

 

 

All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.