Specifications:
-
- CLR, P/N TR-14
- Inductance = 0.01984 mH +/- 4%
- Ohm = 0.0075 Ohms
- Continuous current: 1200 Amps
- Current limit: 18kA
- Rated voltage: 480 VAC
- Frequency: 60 Hz
- BIL across coil: 60 kV
- BIL across base insulator: 45 kV
- Available fault current: 45.9 kA
- Number of coil per phase: 1
- Mounting (side-by-side or three phase stack): Three Phase Stack
- MC1 / MC2 above and below edge of coil: 3 / 15 inch
- MC1 / MC2 from side to the edge of coil: 7/ 10 inch
- Approx. Packing Dimensions (inch): 50 x 50 x 95
- Estimated weight: 1400 lbs.
The customer application is shown below:
The details of the CLR are shown below. Three CLR’s are used for a three phase applications. Three CLR’s are installed three stack high. Drawing belongs to Trench Limited.