CLR, 0.011 mH, 1500 Amps, 380 VAC
P/N TR-11

Specifications:

    • CLR, P/N TR-11
    • Inductance = 0.011 mH +/- 4%
    • Ohm  = 0.004147 Ohms
    • Continuous current: 1500 AmpsEdit Page
    • Current limit: 30 kA
    • Rated voltage: 380 VAC
    • Frequency: 50 Hz
    • BIL across coil: 20 kV
    • BIL across base insulator: 20 kV
    • Available fault current: 76 kA
    • Number of coil per phase: 1
    • Mounting (side-by-side or three phase stack): side-by-side
    • MC1 / MC2 above and below edge of coil: 295 / 295 mm
    • MC1 / MC2 from side to the edge of coil: 300 / 300 mm
    • Overall dimensions (mm): 1300″W x 1300″L x 900″H
    • estimated weight: 175 lbs.

The customer application is shown below:

 

 

The details of the CLR are shown below. Three CLR’s are used for a three phase applications. Three CLR’s are installed side-by-side. Drawing belongs to Trench Limited.

 

 