CLR, 0.011 mH, 1500 Amps, 380 VAC
P/N TR-11
Specifications:
-
- CLR, P/N TR-11
- Inductance = 0.011 mH +/- 4%
- Ohm = 0.004147 Ohms
- Continuous current: 1500 AmpsEdit Page
- Current limit: 30 kA
- Rated voltage: 380 VAC
- Frequency: 50 Hz
- BIL across coil: 20 kV
- BIL across base insulator: 20 kV
- Available fault current: 76 kA
- Number of coil per phase: 1
- Mounting (side-by-side or three phase stack): side-by-side
- MC1 / MC2 above and below edge of coil: 295 / 295 mm
- MC1 / MC2 from side to the edge of coil: 300 / 300 mm
- Overall dimensions (mm): 1300″W x 1300″L x 900″H
- estimated weight: 175 lbs.
The customer application is shown below:
The details of the CLR are shown below. Three CLR’s are used for a three phase applications. Three CLR’s are installed side-by-side. Drawing belongs to Trench Limited.
All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.