CLR, 0.00272 mH, 4000 Amps, 480 VAC
P/N TR-02A
Specifications:
-
- CLR, P/N TR-02A
- Inductance = 0.00272 mH +/- 5%
- Ohm = 0.001 Ohms
- Continuous current: 4000 Amps
- Current limit: 74.5 kA
- Rated voltage: 480 VAC
- Frequency: 60 Hz
- BIL across coil: 30 kV
- BIL across base insulator: 95 kV
- Mechanical peak current: 114.7 kA
- Losses at fundamental current (75 C ) per phase: 2.9 kW
- Number of coil per phase: 1
- Mounting (side-by-side or three phase stack): side-by-side
- MC1 / MC2 above and below edge of coil: 3 / 9 inches
- MC1 / MC2 from side to the edge of coil: 7 / 9 inches
- Overall dimensions: 34″W x 36″L x 38″D
- estimated weight: 250 lbs.
The customer application is shown below:
The details of the CLR are shown below. Three CLR’s are used for a three phase applications. Three CLR’s are installed side-by-side. Drawing belongs to Trench Limited.
All our CLR’s are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.