CLR, 55 uH, 300 Amps, 480 VAC, 3 PH, 60 Hz, P/N BA-02
The calculations of the inductance are shown below:
-
- V L-L = 480 VAC
- V L-N = 277 VAC
- Frequency = 60 Hz
- Desired Fault Current IL1: 10000 Amps
- Available Fault Current IL2= 25000 Amps
- L = [1.25 x V L-N x (1/ IL1 – 1/ IL2)] / (2 x π x 60)
- Inductance = [1.25 x 277 x (1/10000 – 1/25000)] / (2 x 3.142 x 60) = 55 uH
Specifications:
-
- Air Core Reactor, P/N BA-02
- Inductance = 55 uH
- Impedance = 20.7 milliohms
- Continuous current: 300 Amps
- Available fault current: 25000 Amps
- Limit fault current: 10000 Amps
- Voltage: 480 VAC L-L
- Three inductors are required for one complete CLR system
- Enclosure dimensions: 111”H x 54”W x 54”D
- Estimated weight: TBD