THREE PHASE HIGH CURRENT TRANSFORMER
100 KVA, OUTPUT 12 VAC, 4810 AMPS, P/N 19257B
Specifications:
- Multi Tap Transformer: 100 KVA, 3 PH, 60 Hz, P/N 19257B
- Primary: 480 VAC, 120 Amps, Delta
- Secondary: 6.0 / 7.5 / 9.0 / 10.5 / 12.0 VAC L-L, 4810 Amps, Open Delta
- Secondary taps are on the primary side
- Customer is responsible for making Closed Delta connections on the secondary
- If 480 VAC is connected to Primary (1,1,1), Secondary (A to F) is 12.0 VAC
- If 480 VAC is connected to Primary (2,2,2), Secondary (A to F) is 10.5 VAC
- If 480 VAC is connected to Primary (3,3,3), Secondary (A to F) is 9.0 VAC
- If 480 VAC is connected to Primary (4,4,4), Secondary (A to F) is 7.5 VAC
- If 480 VAC is connected to Primary (5,5,5), Secondary (A to F) is 6.0 VAC
- Primary copper bus bars are 1/4″ x 1″ with one hole
- Secondary copper bus bars are 4″ x 1/2″ thick with eight holes
- Three temperature sensors are installed on the primary windings for ON/OFF control
- Copper winding construction
- Open core and coil: 30″H x 30″W x 30″D approximately
- Weight: 1400 lbs. approximately
The photo of the transformer is shown below:
The details of the transformer are shown below:
To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.