THREE PHASE MULTI TAP TRANSFORMER
20 KVA, P/N 19117N

Specifications:

  • Isolation Transformer, 20 KVA, 3 PH, 50/60 Hz, P/N 19117N
  • Primary: 440 / 480 VAC L-L, 26.2 Amps max, Wye with a neutral
  • Secondary: 230 VAC L-L, 50 Amps, Delta
  • Copper winding construction
  • Primary and secondary Copper bus bars are 1/8″ x 5/8″ with one hole
  • Indoor enclosure, 24″H x 18″W x 16″D
  • All connections are inside the enclosure

The photo of the enclosure and the transformer is shown below:

 

PHOTO, PN 19117N

 

The schematic diagram is shown below:

 

SCHEMATIC, PN 19117N

 

To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.