12-PULSE 520 KVA PHASE-SHIFT TRANSFORMER

Specifications:

  • 12-Pulse Transformer: 520 KVA, 3 PH, 60 Hz, P/N 10370L3
  • Primary (H1, H2, H3): 480 VAC L-L, Delta, 626 Amps
  • Secondary A (X1, X2, X3): 480 VAC L-L, Delta, 313 Amps, 260 KVA
  • Secondary B (Y1, Y2, Y3): 480 VAC L-L, Wye, 313 Amps, 260 KVA
  • Application: Variable-speed drive (VSD) for electrical submersible pump
  • Copper windings
  • ONAN Cooling – Non-PCB Mineral Oil
  • Temperature Rise: 65 degrees C
  • Dimensions: 84” W x 66” H x 52” D
  • NEMA 3R Enclosure
  • Core: 2300 lbs.
  • Copper: 1300 lbs.
  • Estimated weight: 9000 lbs. or TBD

The photo of the enclosure is shown below.