750 KVA, 24-Pulse Phase-Shifted Oil-Filled Transformer

Specifications:

  • 24-Pulse Transformer, 750 KVA, 3 PH, 60 Hz, P/N 10290L1
  • Primary: 480 VAC L-L, Delta
  • Secondary: Four isolated 480 VAC, 3 PH extended Delta phase-shifted outputs
  • Nominal Phase Shifts: -22.5°, -7.5°, +7.5°, +22.5°
  • Copper Windings
  • ONAN Cooling
  • Temperature Rise: 65 °C
  • Non-PCB Mineral Oil
  • NEMA 4X Stainless Steel Enclosure, 316L
  • Total Dimensions: 96” W x 72” D x 86” H
  • Total Weight: 9,000 lbs.

A photo of the complete transformer is shown below:

1. Specifications

Preliminary Electrical Performance

2. Construction Details

Core
• Three-leg grain-oriented silicon-steel core, low-loss step-lap/mitered construction.
• Conservative flux-density design for harmonic VSD duty and reduced excitation/noise.
• Core grounded at one controlled point; clamps arranged to minimize circulating currents.

Windings
• Copper primary winding, 480 V Delta.
• Four separate 480 V extended-delta secondary winding systems, each feeding one identical 6-diode bridge.
• Secondary voltage, winding resistance and leakage impedance to be closely matched to promote equal bridge loading.
• Oil-compatible cellulose/pressboard winding insulation and barriers.
• Electrostatic shielding between primary and secondary systems is recommended for VSD/ESP service.

Tank, Cooling and Offshore Protection
• Welded carbon-steel oil tank with carbon-steel ONAN radiator banks.
• Special offshore coating system: abrasive blast preparation, zinc-rich primer, high-build epoxy intermediate coat and
marine/offshore topcoat or customer-approved equivalent.
• NEMA 4X stainless-steel terminal/control enclosure; 316L preferred.
• ONAN radiator system sized with thermal margin for harmonic and stray losses.

Reservoir / Conservator
• Separate external reservoir is not required.
• Recommended construction is a sealed-tank design with adequate internal expansion/head space for mineral-oil volume
change.
• Provide pressure/vacuum gauge and pressure-relief device.

Preliminary Losses, Thermal Performance, Size and Weight

To discuss your specific application, please call our number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.

CONTACT FOR A FREE QUOTE

Need a replacement for urgent and obsolete transformers and inductors?

Our engineers can respond within the hour.

EMAIL: quote@lcmagnetics.com

PHONE: (714) 624-4740

L/C MAGNETICS INC.

MANFACTURER, RESELLER, AND DISTRIBUTOR OF CUSTOM TRANSFORMERS AND INDUCTORS

DRY TYPE TO OIL FILLED PRODUCTS FROM 0.1 KVA TO 50 MVA

CELEBRATING 35 YEARS IN BUSINESS

CARL E. HOLMES COMPANY -- CEHCO

MANUFACTURER OF CUSTOM DC RECTIFIERS, TRANSFORMER RECTIFIER ASSEMBLIES, AND POWER SUPPLIES

DIVISION OF L/C MAGNETICS

RECTIFIER SPECIALIST SINCE 1945