400 Hz THREE PHASE ISOLATION TRANSFORMER 12 KVA, P/N 19771N3

Specifications:

  • Isolation Transformer: 12 KVA, 3 PH, 400 Hz, P/N 19771N3
  • Primary: 208 VAC L-L, 33.3 Amps, Wye with neutral (N), 120 VAC L-N
  • Secondary: 115 VAC L-L, 60.2 Amps, Delta
  • Copper windings
  • Approvals: None
  • Primary and secondary copper bus bars are 1/8″ x 5/8″ with one hole
  • 4 MIL E Core will be used to fabricate the transformer
  • NEMA 3R enclosure: 24″H x 18″W x 24″D
  • Estimated weight: 200 lbs.
  • 400 Hz transformers are inherently noisy. It does not affect the function of the unit.

 

The photo of the transformer and the enclosure is shown below:

 

 

The schematic diagram is shown below:

 

 

To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.